Menu Path
Parameter
ASN
Params & Display>
ProductionDate
Burner Control>
SerialNumber
Product ID
ParamSet Code
ParamSet Vers
Params & Display>
SW Version
Burner Control
HomePosGas or
HomePosOil
HomePosAir
Params & Display>
RatioControl>
HomePosAux1
Gas/Oil Settings>
Special Positions>
HomePosAux2
HomePos
HomePosAux3
HomePosAux3
HomePosVSD
PrepurgePosAir
PrepurgePosAux1
Params & Display>
RatioControl>
Gas/Oil Settings>
PrepurgePosAux2
Special Positions>
PrepurgePos
PrepurgePosAux3
PrepurgePosVSD
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
Product version identification.
Date LMV unit was produced.
Serial number of unit.
Parameter set code.
U
Version (revision) of the tagged parameter set.
LMV software version.
Sets the home position of the fuel actuator(s). The fuel actuator(s) will also stay in this position during
prepurge. Each fuel can have its own setting.
Range = 0º - 90º, Def = 0º. Typ = 2º from valve / damper mechanical stop.
Sets the home position of the air actuator. Each fuel can have its own setting.
Range = 0º - 90º, Def = 0º Typ = 2º from valve / damper mechanical stop.
Sets the home position of the aux1 actuator. Each fuel can have its own setting.
Range = 0º - 90º, Def = 0º Typ = 2º from valve / damper mechanical stop.
Sets the home position of the aux2 actuator. Each fuel can have its own setting.
Range = 0º - 90º, Def = 0º Typ = 2º from valve / damper mechanical stop.
Sets the home position of the aux3 actuator. Each fuel can have its own setting.
Range = 0º - 90º, Def = 0º Typ = 2º from valve / damper mechanical stop.
S
Sets the home position of the VSD. Each fuel can have its own setting.
Range = 0 to 100 %, Def = 0 Typ = 0
Sets the prepurge position of the air actuator.
Range = 0º - 90º Def = 90º Typ = 60º to 85º.
Sets the prepurge position of the aux1 actuator.
Range = 0º - 90º Def = 90º Typ = at least 2º from valve / damper mechanical stops.
Sets the prepurge position of the aux2 actuator.
Range = 0º - 90º Def = 90º Typ = at least 2º from valve / damper mechanical stops.
Sets the prepurge position of the aux3 actuator.
Range = 0º - 90º Def = 90º Typ = at least 2º from valve / damper mechanical stops.
Sets the prepurge position of the VSD.
Range = 10 to 100% Def = 100% Typ = At least 60%.
Sec 4 Pg 34
Descriptions / Notes
All
10-12
10-12
24
www.scccombustion.com