Menu Path
Parameter
Date
TimeOfDay
BU included?
AZL included?
LC included?
ACT1 included?
Updating>
ParamsBackup>
ACT2 included?
BackupInfo
ACT3 included?
ACT4 included?
ACT5 included?
ACT6 included?
VSD included?
O2 included?
LMV5x -> AZL
Updating>
Param Backup
P
B
k
AZL -> LMV5x
Updating
Load_SW_from_PC
Access w-out PW
PW Login
Access Serv
Access OEM
PW Logout
PW Logout
LossFlameTest
SLT Test
SafetyCheck
Funct
SLT-Testload Mod
SLT-Testload Stg
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
This displays the date of the last back-up.
This displays the time of day of the last back-up.
This states if the Basic Unit (LMV) was included in the last back up.
This states if the AZL was included in the last back up.
This states if the LC (Load controller) was included in the last back up.
This states if the Act 1 (Actuators 1) was included in the last back up.
U
This states if the Act 2 (Actuators 2) was included in the last back up.
This states if the Act 3 (Actuators 3) was included in the last back up.
This states if the Act 4 (Actuators 4) was included in the last back up.
This states if the Act 5 (Actuators 5) was included in the last back up.
This states if the Act 6 (Actuators 6) was included in the last back up.
This states if the VSD (Variable Speed Drive) was included in the last back up.
This states if the O2 module was included in the last back up.
Transfers a parameter set from the LMV5x to the AZL.
Transfers a parameter set from the AZL to the LMV. Useful for transferring parameter sets to identical
burners. NOTE : Each burner must have a UNIQUE burner ID for safety purposes. NOTE : When
transferring parameter sets from the AZL to the LMV5, do not stop the transfer until Backup Restore
transferring parameter sets from the AZL to the LMV5 do not stop the transfer until "Backup Restore
S
S
Finished Parameter BC : complete or BC : partial" is shown on the AZL screen. This could take up to 5
minutes. "backup restore is carried out" means that the back-up restore is in progress. Do not disturb the
LMV5 while the back-up restore is in progress.
Enables software updates on the AZL5x with a PC tool
U Access w-out PW (with-out PassWord). Also called User level.
S Obtaining access rights requires the correct Service Level password
O Obtaining access rights requires the correct OEM Level password
Selection reduces access to Access w-out PW, also called User level.
S
Enables testing of the flame sensor input on the LMV by momentarily interrupting the flame signal.
This enables the testing of the safety limits. Range = activated, deactivated. activated - The internal load
controller's setpoint AND switch-off threshold will be ignored, allowing a test of a separate high limit control
or pressure relief valve. deactivated - normal operation.
U
Load for the SLT test in modulating operation. Range = 0 to 100% Def = 100% Typ = 50%
This sets the load for the SLT test in staged operation. Range = S1, S2, S3 Def = S3, Typ = S2
Sec 4 Pg 58
Descriptions / Notes
All
60-62