Initial Value Input X; Logic Input X - ABB tacteo KNX Product Manual

Room outdoor sensor
Table of Contents

Advertisement

11.7.4.5

Initial value input x

Options:
Initialised with 0:
After initial commissioning and after the return of voltage the input has the logical value
"0".
Initialised with 1:
After initial commissioning and after the return of voltage the input has the logical value
"1".
The parameter is used to specify the value the input is to have after initial commissioning and
after the return of voltage. Thus, no undefined states can arise.
11.7.4.6

Logic input x

Options:
Normal:
The input signal of the channel is not inverted.
Inverse:
The input signal of the channel is inverted.
The parameter is used to invert the input signal of the channel.
Note
For a 1-byte size input object, the "inverse" setting means that only upon receipt
of the value "0" will a logical "1" be present on the input. All other values (1 to
255) cause a logical "0" on the input.
Product manual 2CKA001473B9488
Description of application and parameters
Initialised with 0
Initialised with 1
Normal
Inverse
Application "General functions"
│155

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus knx

Table of Contents