11.5.14.1

Duration of long operation

Options:
The application can differentiate between a short and a long press of the button. At a short
press of the button a telegram with the command "Move/position blind" is sent on the bus. At a
long press of the button a telegram with the command "Adjust/position slats" is sent.
The parameter is used to specify the time after which a long button press is recognised. A
telegram is sent on the bus via communication object "Sx: adjust" or "Sx: slat position" only after
this time has expired. A typical value for a long press of the button is 0.4 seconds.
Note
The command "Adjust/position blind" is sent immediately after the press of the
button. The command is also sent if the button is pressed long and a
"Adjust/position slats" command is sent due to the long operation. This causes a
short jerking of the blind since the first slats adjustment command is always
interpreted by a blind actuator as a stop command.
11.5.14.2

Object type

Options:
1 bit:
The value is sent as 1-bit switching commands (up/down or adjustment).
1 byte 0 - 100%:
The value is sent as 1-byte value without a sign (position in percent).
The parameter is used to set the size of communication objects for the control of blinds. For
selection "1 bit", objects "Sx: moving" and "Sx: adjusting" are available. For selection "1 byte 0-
100%", objects "Sx: position" and "Lx: slat position" are available.
If option "1 byte 0-100%" is selected, communication objects can be connected with 1-byte
position objects of the blind actuators. Also desired positions of the blind can be preset under
Extended parameters.
Example: Button 1 always moves the blind down to 50%, with the slats closed at 50%. Button 1
always moves the blind down to 80%, with the slats closed at 100%.
Product manual 2CKA001473B9488
Description of application and parameters
Setting option from 00.300 to 03.000 (ss.fff)
1 bit
1 byte 0 - 100%
Application "Function block x"
│117