11.5.5.3

Reaction on long operation

Options:
No reaction:
No telegram is sent at a long press of the button.
Value 1:
Value 1 is sent at a long press of the button.
Value 2:
Value 2 is sent at a long press of the button.
Alternating value 1/value 2:
Value 1 and value 2 are sent alternately at a long press of the button.
The parameter is used to specify whether value 1 or value 2 is sent on the bus at a long press
of the button. A further option can be specified as to whether the telegrams are sent alternately.
This means that after value 1 has been sent, value 2 is sent at a renewed press of the button.
After it is pressed again, value 1 is again sent out.
Note
Parameter "Value x for long operation" is used to specify the values that are to
be sent.
11.5.5.4

Duration of long operation

Options:
The application can differentiate between a short and a long press of the button. At a short
press of the button a value is sent on the bus via communication object "Sx: value switching at
short operation". At a long press of the button a value is sent on the bus via communication
object "Sx: value switching at long operation".
The parameter is used to specify the time after which a long button press is recognised. A
typical value for a long press of the button is 0.4 seconds.
Product manual 2CKA001473B9488
Description of application and parameters
No reaction
Value 1
Value 2
Alternating value1/value2
Setting option from 00.300 to 03.000 (ss.fff)
Application "Function block x"
│76