Object value enable object

Options:
Normal:
If an Off telegram is received via the object "GFx: control input", the function "Gate" is
blocked. An On telegram deactivates the blockage.
Inverse:
If an On telegram is received via the object "GFx: control input", the function "Gate" is
blocked. An Off telegram deactivates the blockage.
The parameter is used to specify whether function "Gate" is blocked temporarily at the receipt of
an On or Off telegram.
Note
This parameter can only be set if the "Enable object" parameter is set on
"activated".
11.7.5.7

Enable object after return of voltage

Options:
Blocked:
The enable object is not activated after bus voltage recovery. The blocking function is
deactivated.
Enabled:
If the enable object was activated prior to bus voltage recovery, it will also be activated
after bus voltage recovery.
The parameter serves to ensure that a defined value is present on communication object "GFx:
control input" after a return of bus voltage.
Note
This parameter can only be set if the "Enable object" parameter is set on
"activated".