4 O P E R AT I O N

4 .5 User settings

The following table displays the options that
can be changed by the user.
Table 10: User settings
Submenu
Password
Language
User password
Audible alarm
Output voltage
Output frequency
Power strategy
Auto bypass
Auto restart
Dry in
Dry out
Start on battery
External battery modules
External battery AH setting
Battery remaining time
Charger current
Site wiring fault alarm
LCD contrast
Available settings
Key the password
[English][Deutsch][Español]
[disabled] [Enabled]
[enabled] [disabled]
[208V] [220V] [230V] [240V]
Can be changed in standby
mode and bypass mode
[autosensing] [50HZ][60HZ]
[normal] [high efficiency] [converter]
[enabled] [disabled]
[enabled] [disabled]
Authorize the product to
restart automatically when
mains recovers after a
complete battery discharge.
[Disabled] [SON] [SOFF] [Maintain bypass]
[Load powered] [On battery mode]
[Battery low] [Battery disconnected]
[Bypass output] [UPS normal]
[enabled] [disabled]
[0~20]
[0~300]
[enabled] [disabled]
[0~4] 0~4A for standard model
[0~12] 0~12A for long backup model
[disabled] [enabled]
[-5 ~ +5]
Default settings
USER
English
[disabled]
[enabled]
[230V]
[autosensing]
[normal]
[enabled]
[enabled]
[Disabled]
[Load powered]
[enabled]
According to model
According to model
[enabled]
[4A] for 6-10 kVA
[disabled]
[+0]
25