ABB 8408608 User Manual page 37

Table of Contents

Advertisement

A P P E N D I X A
Appendix A
CS141 SNMP card available parameters (valid for
CS141 Basic, CS141 ModBus, CS141 Advanced) .
The parameters available for CS141 SNMP cards
are shown below.
Parameter
Measurement Parameters
Input Voltage
Input Frequency
Output Voltage
Output Load Percentage
Battery Voltage
Battery Capacity
Temperature
UPS Status Information
On shutdown
On inverter
On battery
UPS Alarms
Battery Low
Input Bad
On Bypass
General Fault
Test In Progress
Shutdown imminent
Diagnose test failed
Units
Type
V
Input
Hz
Input
V
Output
%
Output
V
Battery
%
Battery
°C
Environmental
Available interface
Modbus register
Webserver / Modbus
104
Webserver / Modbus
111
Webserver / Modbus
97
Webserver / Modbus
100
Webserver / Modbus
110
Webserver / Modbus
103
Webserver / Modbus
107
Webserver / Modbus
109
Webserver / Modbus
109
Webserver / Modbus
109
Webserver / Modbus
117
Webserver / Modbus
120
Webserver / Modbus
123
Webserver / Modbus
132
Webserver / Modbus
138
Webserver / Modbus
137
Webserver / Modbus
133
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powervalue 11 rt g2840860784086198408609

Table of Contents