Measuring The Operating Limit Of Set Values - Hitachi Relion 670 Series Commissioning Manual

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506371-UUS Rev. M
X1
ANSI09000735 V1 EN-US
Figure 26:
Table 24:
Test point
1
2
3
4
5
6
Table
24
11.4.2.1

Measuring the operating limit of set values

Procedure:
Line distance protection REL670
Commissioning manual
(
X
1
4
85%
ArgNegRes
6
50% RLdFwd
0.5·RFltFwdPP
Operating characteristic for phase selection function, forward direction phase-to-
phase faults
Test points for phase-to-phase loops A-B (Ohm/phase)
Reach
Value
X
X1
R
0
X
0
R
RLdFwd
R
0.5·RFLdFwPP
X
0.85·X1
R
0.85·X1·1/tan(60°)+0.5 RFLdFwdPP
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
X
0.5·RFLdFwdPP·tan (ArgLd)
R
0.5·RFLdFwdPP
X
-0.5·RLdFwd·tan (ArgDir)
R
0.5·RLdFwd
is used together with figure 26.
© 2017 - 2023 Hitachi Energy. All rights reserved
W
/
phase
)
3
LdAngle
5
60°
2
7
ArgDir
ANSI09000735-1-en.vsd
Comments
When RLdFWd < 0,5·RFLdFwPP
When RLdFwd > 0,5·RFLdFwPP
R=0.491·X1+0.5 RFLdFwdPP
Can be limited by RFLdFwPP
Only when RLdFwd < RFLdFwPP
Testing functionality by secondary injection
W
(
/
phase
)
R
Section 11
M13906-73 v6
97

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rel670

Table of Contents