Hitachi Relion 670 Series Commissioning Manual page 176

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
Table 39:
Set value: Mode
A, B, C
Arone
PosSeq
AB
BC
CA
A
B
C
2.
Adjust the injected current and voltage to the set values in % of IBase and VBase (converted to
secondary current and voltage). The angle between the injected current and voltage shall be set
equal to the set direction Angle1, angle for stage 1 (equal to 0° for low forward power protection
and equal to 180° for reverse power protection). Check that the monitored active power is equal to
100% of rated power and that the reactive power is equal to 0% of rated power.
3.
Change the angle between the injected current and voltage to Angle1 + 90°. Check that the
monitored active power is equal to 0% of rated power and that the reactive power is equal to 100%
of rated power.
170
Calculation modes
Formula used for complex power calculation
=
S
V
A
EQUATION2055 V1 EN-US
=
S
V
AB
EQUATION2056-ANSI V1 EN-US
= ×
S
3
V
PosSeq
EQUATION2057-ANSI V1 EN-US
=
S
V
AB
EQUATION2058-ANSI V1 EN-US
=
S
V
BC
EQUATION2059-ANSI V1 EN-US
=
S
V
CA
EQUATION2060-ANSI V1 EN-US
= ×
S
3
V
EQUATION2061-ANSI V1 EN-US
= ×
S
3
V
EQUATION2062-ANSI V1 EN-US
= ×
S
3
V
C
EQUATION2063-ANSI V1 EN-US
© 2017 - 2023 Hitachi Energy. All rights reserved
*
*
*
×
+
×
+
×
I
V
I
V
I
A
B
B
C
C
*
*
×
-
×
I
V
I
A
BC
C
*
×
I
PosSeq
*
*
×
-
(
I
I
)
A
B
*
*
×
-
(
I
I
)
B
C
*
*
×
-
(
I
I
)
C
A
*
×
I
A
A
*
×
I
B
B
*
×
I
C
1MRK506371-UUS Rev. M
(Equation 80)
(Equation 81)
(Equation 82)
(Equation 83)
(Equation 84)
(Equation 85)
(Equation 86)
(Equation 87)
(Equation 88)
Line distance protection REL670
Commissioning manual