11.
Reset the ENABLE binary input.
12.
Switch the fault current on.
No TRIP signal should appear.
13.
Disable the fault current.
11.5.9.3
Completing the test
Continue to test another function or end the test by changing the TESTMODE setting to Disabled.
Restore connections and settings to the original values, if changed for testing purposes.
11.5.10
Overcurrent protection with binary release BRPTOC
Prepare the IED for verification of settings outlined in Section
Logical signals for BRPTOC protection are available on the local HMI under Main menu /Settings /IED
Settings /Current protection /OvercurrBinRel (50, 2I>) /BRPTOC (50, 2I>):x .
Logical signals for BRPTOC protection are available on the local HMI under Main menu /Settings /IED
Settings /Current protection /OvercurrBinRel (50, 3I>) /BRPTOC (50, 3I>):x .
The Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
11.5.10.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
J
L
M
11.5.10.2
Measuring the operate limit of set values
1.
Check that the input logical signals BLOCK and BLKTR and the output logical signal TRIP are all
logical zero.
2.
If required, activate the input ENABLE on the BRPTOC function block.
3.
Set MeasType to DFT for overcurrent operation.
4.
For a short while inject a current (fault current) in phase A to about 110% of the set operating
current I>, and switch the current off.
Observe to not exceed the maximum permitted overloading of the current circuits in the IED.
Line distance protection REL670
Commissioning manual
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
-
2.2.4
-
2.2.5
New function release
2.2.6
-
2.2.6
-
© 2017 - 2023 Hitachi Energy. All rights reserved
Testing functionality by secondary injection
GUID-EB5AEFC4-6F51-4E1E-8055-4FEC53CA81FD v3
"Preparing the IED to verify
GUID-23898A65-D896-479E-9122-E8D9D6CC4FEB v2
GUID-4FF9AAC6-04B7-4A26-9093-C199C0C50540 v5
Section 11
M14922-50 v4
settings".
167

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rel670

Table of Contents