Hitachi Relion 670 Series Commissioning Manual page 72

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
2.4. Set the Device ID Code in PMU Connection Tester per PMU Data Stream ID Number
2.5. Make sure that the Configure Alternate Command Channel is set as Not Defined. The
2.6. Continue to the section
3.
Set the Connection Parameters on PMU Connection Tester for UDP communication according to
the PMU configuration.
IEC140000136 V1 EN-US
3.1. Set the Local Port to UDP destination port defined in the PMU under the parameter
3.2. Click the Configure Alternate Command Channel to configure the TCP channel. A new
3.3. Set the Host IP as the PMU IP address configured for the port in use. Here the LANAB:1
66
(IDCODE). The PMU Data Stream ID Number is a user assigned ID number (1-65534) for
each data stream sent out from the PMU and it is defined under parameter
PMUdataStreamIDCODE. ( Main menu /Configuration /Communication /Station
communication /phasor measurement /PMU Report /PMUREPORT:1 )
Configure Alternate Command Channel is used to configure a TCP channel to control the
UDP data communication and transfer the header, configuration and command frames.
Verifying the IEEE C37.118/1344 TCP
UDPDestPort1 (Default value: 8910).
window will pop up. A TCP channel needs to be configured in order to control the UDP data
communicatiuon and transfer the header, configuration and command frames.
IEC140000137 V1 EN-US
IPAddress (192.168.1.10) is set.
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK506371-UUS Rev. M
communication.
IEC140000136-1-en.vsd
IEC140000137-1-en.vsd
Line distance protection REL670
Commissioning manual