Forcing By Using Pcm600 - Hitachi Relion 670 Series Commissioning Manual

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506371-UUS Rev. M
IEC15000022 V1 EN-US
Freezing a signal value without changing it
Set the status of a signal to Forced, in the forcing menu that corresponds to the I/O card in question.
See example of LHMI menu in figure
IEC15000020 V1 EN-US
Figure 22:
The signal "freezes" and will not change value even if, for example, a binary input signal voltage changes
level, or if a binary output is activated as the result of a protection function block activating.
10.8.3.2

Forcing by using PCM600

In PCM600 the concept is a bit different compared to LHMI.The forcing is accomplished by entering a
forcing session. Within such a session, multiple signals on multiple I/O boards may be edited and
changed at the same time and has no effect on the IED. Once the user is satisfied with the forcing setup,
then all the changes can be effectuated simultaneously towards the IED, potentially changing inputs and
outputs on multiple I/O boards at the same time. It is also possible to abort this operation (described in
step 6 below) and to
Line distance protection REL670
Commissioning manual
It is possible to power-cycle the IED in this state without losing the forcing states and values.
This means that once a signal is forced, and the IED remains in IED test mode, the input or
output will appear "frozen" at the value selected by the user, even if the IED is switched off
and back on again.
Example of LHMI menu using BIM3
undo all
forcing.
© 2017 - 2023 Hitachi Energy. All rights reserved
22
Section 10
Testing IED operation
GUID-FD76AAC1-7098-47D3-A3A1-6ACDF509ED91 v1