Section 11
Testing functionality by secondary injection
11.5.8.15
Completing the test
Continue to test another function or end the test by changing the TESTMODE setting to Disabled.
Restore connections and settings to the original values, if changed for testing purposes.
11.5.9
Stub protection STBPTOC (50STB)
Prepare the IED for verification of settings outlined in Section
Logical signals for STBPTOC (50STB) protection are available on the local HMI underMain menu /
Settings/IED Settings /Current protection/Stub(PTOC,50STB) /STBPTOC:x
11.5.9.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
J
L
M
11.5.9.2
Measuring the trip limit of set values
1.
Check that the input logical signals BLOCK and ENABLE and the output logical signal TRIP are all
logical zero.
2.
Activate the input ENABLE on the STBPTOC (50STB) function block
3.
For a short while inject a current (fault current) in one phase to about 110% of the set operating
current, and switch the current off.
Observe to not exceed the maximum permitted overloading of the current circuits in the IED.
4.
Switch the fault current on and measure the operating time of STBPTOC (50STB).
Use the TRIP signal from the configured binary output to stop the timer. The operation should be
instantaneously.
5.
Activate the input BLOCK on the STBPTOC (50STB) function block.
6.
Switch on the fault current (110% of the setting).
No TRIP signal should appear.
7.
Switch off the fault current.
8.
For a short while inject a current (fault current) in same phase to about 90% of the set operating
current, and switch the current off.
9.
Switch the fault current on.
No TRIP signal should appear.
10.
Switch off the fault current.
166
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
-
2.2.4
-
2.2.5
-
2.2.6
-
2.2.6
-
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK506371-UUS Rev. M
"Preparing the IED to verify
GUID-D32C2C38-452F-45B0-85C1-6C9542089357 v2
Line distance protection REL670
Commissioning manual
M12104-72 v6
M14922-2 v8
settings".