14.4.9 Writing commands

Writes a sequence program to the FX PLC. (Overwrite/Insert)
Writing basic commands
1
(1) Operations
(a) Inputting command only (Ex.: ANB, ORB command etc.)
Stop the FX PLC
(b) Inputting command and device (LD, AND commands etc.)
Stop the FX PLC
Input the device name and device number
(c) Inputting command, No. 1 device, No. 2 device (MC, OUT (T, C) commands, etc.)
Stop the FX PLC
SP
Moving the cursor to the position to write the command
(2) Example
(a) Writing ORB command
Stop the FX PLC
MODE
With
cursor to the position to
overwrite/insert the command.
Input the command
MODE
For overwriting: (WRITE mode)
For insertion: (INSERT mode)
MODE
For overwriting: (WRITE mode)
For insertion: (INSERT mode)
Input the command
MODE
For overwriting: (WRITE mode)
For insertion: (INSERT mode)
Input the device name and device number
When starting to write a command, place the cursor on the command line (the line
on which the step number is displayed).
You cannot write a command with the cursor on an operand or set value line.
2 LDI
M
100
3 MOV
D
D
< READ >
Set the
WRITE or
< WRITE >
INSERT
mode
or
, move the
GO
Input the command
GO
Input the device name and device number
GO
Command line (Place the cursor on this line.)
12
0
Operand, set value line (Cannot operate on this line.)
10
4 LDI
5 AND
6 NOP
7 NOP
ORB
4 LDI
5 AND
6 ORB
7 NOP
14.4 MELSEC-FX List Editor
14.4.9 Writing commands
X
004
X
005
GO
X
004
X
005
14 - 97
9
10
11
12
13
14
15