7.1.2

The cause of malfunctions related wiring/Remedy

Grounding of the GOT may cause electric potential difference and noise interference, which may result in
GOT malfunctions.
These problems may be resolved by taking the following measures.
Wiring path of the GOT's ground cable and power line
1
Bundling the GOT's ground cable and power line together can cause interference noise, which may
result in malfunctions.
Keeping the GOT's ground cable and power line away from each other will help minimize noise
interference.
Power supply for power equipment
Good : Wiring the ground cable away from the
power cable
Connecting the ground cable from the panel that houses control equipment to the
2
panel to which the GOT is grounded
When running a single ground cable from the panel that houses such piece of control equipment as a
sequencer to the panel to which the GOT is grounded, the ground cable may have to be directly
connected to the terminal on the GOT.
If electric potential difference between the ground points created by it causes malfunctions, lowering the
voltage as shown in Remedy 1 below may solve the problem.
7 - 4
7.1 Power Supply Wiring
7.1.2 The cause of malfunctions related wiring/Remedy
FG
Connection cable
Ground cable from
the panel that
houses control
equipment
FG
Power supply for power equipment
Bad : Bundling the ground cable and
the power cable
FG