5.2.3 Technical Specifications

Table 5-5 General specifications
Item
Specifications
Cooling mode
Air cooled
Refrigerant
R410A
Air flow mode
Horizontal air flow
Dimensions (H
2000 mm x 300 mm x 1100 mm (cabinet)
x W x D)
Net weight
230 kg
Environmental
REACH, RoHS
friendliness
Issue 04 (2023-11-10)
Specifications
The inlet water pressure should be in the range of 0.1–0.7 MPa (a
reducing valve must be installed at the humidifier water inlet if the
inlet water pressure exceeds 0.7 MPa), and the temperature should
be in the range of 1°C–40°C.
The wet film humidifier uses tap water and does not require an
additional water treatment device at the water inlet. The water
requirements are as follows:
● Non-freezing and nephelometric turbidity units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L
The distance between the top drainage of the water pump and the
cabinet installation floor should not exceed 4 m.
Leakage circuit breakers are not recommended for the main power
supply route. If a leakage circuit breaker is required by the customer
or local regulations, select the residual current circuit breaker
(RCCB) that is insensitive to single-phase DC pulsation and transient
impulse current.