FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
Figure 7-3 Water fire extinguishing pipe network
Before starting water fire extinguishing in the lithium battery scenario, press the
EPO button to power off the lithium battery and turn off the upstream switch of
the input Power PDB.
Location Deployment Requirements
Safety Requirements for Fire Prevention and Control
Must comply with local laws, regulations, and standards on fire safety, and be
equipped with necessary fire fighting facilities to effectively extinguish fire and
prevent reignition.
Issue 04 (2023-11-10)
NO TICE
Must not be located in environments where explosive gases may exist or be
released.
Must not be located near or below areas with water leakage risks, such as
water reservoirs, water landscapes, and water towers.
Shall comply with local fire protection laws and regulations in aspects such as
production scenarios and the safe distance and layout of buildings and
materials.
Do not store combustible materials in the battery room. Keep such materials
at least 3 m away from this product.
Shall be at least 3 m away from the following places for outdoor deployment:
restricted areas, combustible material warehouses, dangerous goods, high-
stacking warehouses, power infrastructure, public roads, and buildings.
Shall be equipped with fire extinguishers filled with halogenatedane,
heptafluoropropane, perfluorohexanone, carbon dioxide, or dry powder. Each
fire protection unit shall be equipped with at least two fire extinguishers,
which shall be checked and replaced periodically.
Shall be configured with in-room CO sensors, smoke sensors, and temperature
sensors. At least two sensors of each type shall be configured, and the
automatic fire alarm system should be enabled.
Copyright © Huawei Digital Power Technologies Co., Ltd.