Raised Floor - Huawei FusionDC1000A Product Description

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
Item
Installation space
Installation mode
Door opening mode
Weight of an empty cabinet
IP rating

3.6.4 Raised Floor

The raised floor is installed at the smart cooling product side to facilitate pipe
routing for smart cooling products.
Issue 04 (2023-11-10)
The raised floor consists of flooring, legs, beams, and conductive rubber pads.
The floor does not dislocate or deform after long range transportation, and is
easy to assemble and maintain.
The legs can be adjusted in height, and are galvanized to provide efficient
anti-corrosion performance.
The compression strength of both the raised floor and legs is greater than
2
1500 kg/m
.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Technical Specifications
● 42 U available space
● The distance between the front and rear
mounting bars can be adjusted for every 25
mm.
– For a 1200 mm deep cabinet: The
maximum depth for installing devices
inside the cabinet is 750 mm and can be
extended to 850 mm by adjusting the
mounting bars.
– For a 1100 mm deep cabinet: The
maximum depth for installing devices
inside the cabinet is 700 mm and can be
extended to 750 mm by adjusting the
mounting bars.
– If the depth of the equipment exceeds
the specifications, the cabinet needs to
be customized by raising RM
requirements.
● Positions for vertically installing two rPDUs
are provided in the rear of the cabinet.
Supports installation on a base and raised
floor.
The front door is a single door, and the rear
door is a double one.
● 2000 mm x 600 mm x 1100 mm: 110 kg
● 2000 mm x 600 mm x 1200 mm: 130 kg
NOTE
The weight of an empty cabinet includes the weight
of the front and rear doors.
IP20
3 Structural system
17