Huawei FusionDC1000A Product Description page 92

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
Item
PAD
intelligent
charging
BLINK
button
Indicators
Table 6-25 AC actuator indicators
Indica
tor
Power
RUN
ALM
Issue 04 (2023-11-10)
Specifications
Charging stops when the PAD battery level reaches 100%. When
the battery level is lower than 40% (default value, which can be
set to 30, 40, or 50), charging starts.
● Press the button for less than 1 second to start blinking.
● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.
Color
Name
Green
Power status
indicator
Green
Running
status
indicator
Red
Alarm
indicator
Copyright © Huawei Digital Power Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power is abnormal or the
board program is loading.
Blinking at
The AC actuator successfully
long
registers with the ECC800-Pro
intervals
and the software runs properly
(the indicator blinks at 0.5 Hz,
on for 1s and then off for 1s).
Blinking at
The communication fails or
short
the AC actuator fails to
intervals
register with the ECC800-Pro
(the indicator blinks at 4 Hz,
on for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 5s.
Steady on
A system failure alarm is
generated.
Off
No system alarm is generated.
6 Management System