NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)
Menu
T/H Sensor
Issue 02 (2022-03-30)
Parameter
Floor water
overflow alarm
action
In-cabinet water
overflow alarm
action
Temperature and
humidity control
type
Temperature
setpoint
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Description
Set the action of the device if there is water
overflow on the floor based on the actual
scenario.
● Shutdown: The device shuts down when
a floor water overflow alarm is
generated.
● Inactivity: The device runs as usual when
a floor water overflow alarm is
generated.
● Only indoor fan running: Only the indoor
fan runs when a floor water overflow
alarm is generated.
● Humidifier stopped: Only the humidifier
is stopped when a floor water overflow
alarm is generated.
Set the action of the device if there is water
overflow in the cabinet based on the actual
scenario.
● Shutdown: The device shuts down when
an in-cabinet water overflow alarm is
generated.
● Inactivity: The device runs as usual when
an in-cabinet water overflow alarm is
generated.
● Only indoor fan running: Only the indoor
fan runs when an in-cabinet water
overflow alarm is generated.
● Humidifier stopped: Only the humidifier
is stopped when an in-cabinet water
overflow alarm is generated.
When the application scenario is non-aisle
containment, you are advised to choose
Return air. Choose Cold aisle if cold aisle
T/H sensors are installed. Hot aisle is not
recommended.
After the temperature and humidity control
type and the temperature value under this
type are set, the device performs regulation
based on the settings.
● Return air: 18–45°C recommended
● Supply air: 15–35°C recommended
● Cold aisle: 15–35°C recommended
● Hot aisle: 18–45°C recommended
71