NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)
Parameter
Temperature setpoint
Humidity setpoint
The relationship between the temperature setpoint and the humidity setpoint is as
follows: Under the condition that the absolute humidity range is [0.0026, 0.0141]
for the default temperature setpoint 23°C and relative humidity range [15% RH,
80% RH], ensure that the absolute humidity range is [0.0026, 0.0141] when you
set the temperature setpoint and humidity setpoint.
Table 4-5 Setting example
Temperature Setpoint
(°C)
15
16
17
18
19
20
21
22
23
24
25
26
27
Issue 02 (2022-03-30)
Description
After the temperature and humidity control type and
the temperature value under this type are set, the
device performs cooling or heating based on the
settings.
● Return air: 26–35°C recommended
● Supply air: 18–24°C recommended
● Cold aisle: 18–24°C recommended
● Hot aisle: 26–35°C recommended
After the temperature and humidity control type and
the humidity value under this type are set, the device
performs regulation based on the settings.
40%–60% is recommended.
Lower Limit of
Humidity Setpoint (%
RH)
24.7
23.2
21.7
20.4
19.2
18
16.9
15.9
15
15
15
15
15
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Upper Limit of
Humidity Setpoint (%
RH)
80
80
80
80
80
80
80
80
80
75.3
70.9
66.9
63
76