Parameter
Teamwork function
Networking mode
Teamwork parameter
synchronization
Number of systems in
this group
Number of running
systems in this group
Issue 02 (2022-03-30)
Description
Specifies whether to enable the teamwork function.
Set this parameter based on onsite heat load
distribution.
● Disable: A unit operates independently.
● Enable: A unit operates in team with other units.
Specifies the networking mode for teamwork control.
The networking mode selected on the screen must
match the actual networking mode. Otherwise, the
teamwork function is unavailable.
If Teamwork function and Teamwork parameter
synchronization are both set to Enable, you can
select Set Local or Set Teamwork when setting
parameters.
NOTE
● Set Local: Set parameters for the local unit.
● Set Teamwork: Set parameters for all units in a
teamwork group.
Specifies the total number of units in this group. The
value is an integer ranging from 1 to 32.
NOTE
This parameter is displayed after Teamwork function is set
to Enable.
Specifies the number of running units in this group.
The value is an integer ranging from 1 to the value
of Number of systems in this group.
NOTE
This parameter is displayed after Teamwork function is set
to Enable.
Copyright © Huawei Technologies Co., Ltd.