4.5 Setting Parameters

4.5.1 Setting T/H Sensor Parameters

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor. The screen
shown in
Figure 4-3 T/H Sensor
Step 2 Set Return air sensor 2 to Enable.
Step 3 Set the temperature and humidity parameters by referring to
Table 4-4 Parameter description
Parameter
Temperature and
humidity control type
Temperature control
mode
Issue 02 (2022-03-30)
If T/H sensors outside cabinets have been deployed in the aisle, enable the
sensors. Otherwise, skip
If you need to enable a T/H sensor, log in as user admin.
This section describes how to enable Return air sensor 2.
Figure 4-3
is displayed.
NO TE
You are not recommended to modify the parameters not listed in
Copyright © Huawei Technologies Co., Ltd.
Step
2.
Description
When the application scenario is non-aisle
containment, you are advised to choose Return air.
Choose Cold aisle if cold aisle T/H sensors are
installed. Hot aisle is not recommended.
The temperature inside the equipment room or aisle is
controlled based on the average value, maximum
value, or minimum value collected by multiple sensors.
4 Power-On Commissioning
Table
4-4.
Table
4-4.