Parameter
WiFi group sharing
enable
Step 3 Tap Submit.
----End

4.5.6 Correlation Relationship of Parameters

When setting parameters, pay attention to the following relationships.
Alarm Parameters
Parameters of Teamwork Settings
Number of smart cooling products in this group ≥ Number of running smart
cooling products in this group
Parameters of Cooling cap. mgt.
Upper limit of water supply temperature > Lower limit of water supply
temperature
Issue 02 (2022-03-30)
Power underfrequency alarm threshold < Power overfrequency alarm
threshold
Backup power underfrequency alarm threshold < Backup power
overfrequency alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
Supply air low temperature alarm threshold + 5°C ≤ Hot aisle low
temperature alarm threshold
Cold aisle low temperature alarm threshold + 5°C ≤ Hot aisle low temperature
alarm threshold
Cold aisle low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
Copyright © Huawei Technologies Co., Ltd.
Description
When a mobile phone is connected to the WiFi of the
smart cooling product, it can access the units in the
same FE cascading network.
4 Power-On Commissioning