Figure A-4 Connecting a hose connector
Step 4 Open the oil drain valve to let the oil slowly move from the transformer to the oil
tank.
Step 5 Check the position indicated by the oil level gauge according to the local ambient
temperature and oil temperature-oil level curve. When the transformer oil drops
to the corresponding indication position, stop draining oil.
Step 6 Close the oil drain valve and remove the hose connector and hose.
Step 7 Reinstall the cover on the oil drain valve.
----End
A.2 How Do I Repair Paint Damage on the Container?
Prerequisites
●
●
Issue 02 (2023-09-30)
Do not apply paint in bad weather, such as rain, snow, strong wind, and
sandstorm, when there is no shelter outdoors.
You have prepared the required paint that matches the color palette delivered
with equipment.