Electrical Installation - Kenwood CKBU 300 Instructions For Use Manual

Built under double oven
Table of Contents

Advertisement

7 - ELECTRICAL SECTION
Before effecting any intervention
on the electrical parts the appli-
ance must be disconnected from
the network.
GENERAL
– The connection to the electrical net-
work must be carried out by qualified
personnel and must be according to
existing norms.
– The appliance must be connected to
the electrical network verifying above
all that the voltage corresponds to the
value indicated on the specifications
plate and that the cables section of
the electrical plant can bear the load
which is also indicated on the plate.
– The appliance can be connected
directly to the mains placing an
omnipolar switch with minimum open-
ing between the contacts of 3 mm
between the appliance and the mains.
– The power supply cable must not
touch the hot parts and must be posi-
tioned so that it does not exceed
75°C at any point.
– Once the appliance has been
installed, the switch must always be
accessible.
32
FEEDER CABLE SECTION
Type HO5RR-F or H05VV-F
~
230 V
3 x 2,5 mm
(**) –
Connection to wall-mounting dis-
tribution panel.
IMPORTANT: this double oven
must be connected to a suitable
double pole control unit adjacent
to the oven.
NO DIVERSITY CAN BE APPLIED
TO THIS CONTROL UNIT.
The connection of the appliance to
the grounding unit is mandatory.
The manufacturer declines every
responsibility for any inconve-
nience resulting from the inobser-
vance of this condition.
2
(**)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents