ABB Endura AZ30 series Programming Manual page 65

Integral probe and remote transmitter combustion oxygen monitor
Hide thumbs Also See for Endura AZ30 series:
Table of Contents

Advertisement

Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
Parameter
...Input/Output
...Current Output 1
Elec. Range Hi
mA
Elec. Range Lo
mA
Output Failure
Disabled
Enabled
Failure Current
Output #1 Test
Table 6.12 Input/Output Menu (Continued)
COI/AZ30E–EN Rev. D
Comment / [Range]
Selects the electrical range high current output value.
[3.80 to 22.00 mA]
Selects the electrical range low current output value.
[3.80 to 22.00 mA]
When Enabled, the current output can be driven to a
preset value if a Failure category diagnostic state
occurs – see page 84.
Sets a preset value that the current output is driven
to when a Failure category diagnostic state is present
– see page 84.
Available only if Output Failure is Enabled.
[3.80 to 22.0 mA]
Selects % output levels for Current Output 1.
When this parameter is exited, the current output
returns to its normal operating value.
[0, 25, 50, 75 or 100 %]
6 Programming
Default
20.00 mA
4.00 mA
Disabled
22.00 mA
0
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents