ABB Endura AZ30 series Programming Manual page 97

Integral probe and remote transmitter combustion oxygen monitor
Hide thumbs Also See for Endura AZ30 series:
Table of Contents

Advertisement

Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
Parameter
Recovery Rate
Calibration /
Accuracy Check
New probe / cell Not applicable –
Time Since Last Cal
Table 9.8 Performance Log Fields (Continued)
COI/AZ30E–EN Rev. D
Comment / Range
The maximum recorded rate of change of the calculated oxygen value when the
test gas is removed and the measurement returns to the process value.
Notes: A valid recovery rate cannot be calculated if:
a manual calibration / accuracy check is performed
either of the test valves are set to manual mode before the test is complete
a subsequent calibration or accuracy check is started before the test is
complete
the difference between the test gas value and process value is less than
10 % of the oxygen range
the maximum rate of recovery is not achieved within 3 minutes of removal of
the test gas
The elapsed time between the last successful calibration and this entry.
is displayed
9 Troubleshooting
95