Pulse operation start, pulse series connection, pulse parallel
connection
LDP, LDF, ANDP, ANDF, ORP, ORF
RnPCPU
RnCPU RnENCPU
(Process)
• LDP: Rising edge pulse operation start
This instruction turns on only at the rising edge (off to on) of the specified bit device.
• LDF: Falling edge pulse operation start
This instruction turns on only at the falling edge (on to off) of the specified bit device.
• ANDP: Rising edge pulse series connection, ANDF: Falling edge pulse series connection
These instructions perform an AND operation with the previous operation result.
• ORP: Rising edge pulse parallel connection, ORF: Falling edge pulse parallel connection
These instructions perform an OR operation with the previous operation result.
Ladder
(s)
LDP
(s)
LDF
ANDP
ANDF
ORP
(s)
(s)
ORF
FBD/LD
EN
ENO
s
■Execution condition
Instruction
LDP
LDF
ANDP
ANDF
ORP
ORF
5 SEQUENCE INSTRUCTIONS
162
5.1 Contact Instructions
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
(s)
(s)
Execution condition
Every scan
ST
ENO:=LDP(EN,s);
ENO:=LDF(EN,s);
ENO:=ANDP(EN,s);
ENO:=ANDF(EN,s);
ENO:=ORP(EN,s);
ENO:=ORF(EN,s);