■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
(d)
Coil
Value
*1 Only C can be used.
*2 T, ST, and C cannot be used.
*3 Only K (decimal constant) can be used.
• In safety programs executed by the Safety CPU, only the following safety devices and constants can be used.
Operand
Bit
SA\X, SA\Y, SA\M, SA\SM, SA\B
(d)
(Set value)
*4 Only SA\C can be used.
*5 SA\T, SA\ST, and SA\C cannot be used.
*6 Only K (decimal constant) can be used.
Processing details
• This instruction increments the current counter value (count value) in the device specified by (d) (in SD language or FBD/
LD, displayed as Coil) by one on the rising edge (off to on) of the operation result up to the OUT instruction. When the count
value reaches the set value (current value  set value), the normally open contact turns on (continuity state) and the
normally closed contact turns off (non-continuity state).
• Counting is disabled while the operation result remains on. (Count input does not need to be converted into pulses.)
• After counting-up, the count value and contact status remain unchanged until the RST instruction is executed.
• When the set value is 0, the same processing is performed as when it is set to 1.
Operation error
There is no operation error.
Word
J\
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
*1
*2
Word
SA\T, SA\ST, SA\C, SA\D, SA\W, SA\SD
*4
*5
Double word
Indirect
specification
Z
LT, LST,
LZ
LC
5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
Constant
Others
K, H
E
$
*3
Constant
K, H
5
*6
185