Concept Of Fail-Safe Digital Control (Door Open/Close) With Emergency Stop Via 3; Digital Inputs - Siemens SIDOOR ATD401W System Manual

Atd4xxw series, door control systems for industrial applications
Hide thumbs Also See for SIDOOR ATD401W:
Table of Contents

Advertisement

3.4.2.10

Concept of fail-safe digital control (door OPEN/CLOSE) with emergency stop via 3

digital inputs

This concept describes one implementation variant of the emergency stop function in
accordance with stop category 1 as specified in EN ISO 13850:2008, with fail-safe control (in
accordance with PLd) of door OPEN/CLOSE drive orders via 3 digital inputs.
Safe motor shutdown
SIDOOR controllers have an internal, cyclically tested and monitored second shutdown route
according to PLd. This ensures safe shutdown of the motor (emergency stop).
The following figures show examples of safe OPEN/CLOSE door control (in accordance with
PLd) with emergency stop in accordance with stop category 0 via 3 digital inputs via
redundant antivalent channel safeguarding.
Figure 3-21
Interfacing safe (PLd) digital door control (OPEN/CLOSE) with emergency stop (encoder type 1) via 3 digital
inputs
Door commands
The door command with the highest priority is STOP → ramp stop.
The status following the ramp stop can be defined using the "special" door command
expansion bit as either "source voltage brake activated" or "coasting down" (deenergized or
no current). In the case of ATD401, the door command expansion bit is permanently set to
"coasting down".
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
SIDOOR functions
3.4 Safety functions
101

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sidoor atd420wSidoor atd410wSidoor atd430w

Table of Contents