Power supply
6.3 SITOP PSU8200 13A/36V 3-phase
6.3.1
Power supply requirements of SITOP PSU8200
NOTICE
SITOP PSU8200 may only be used as of firmware version ATD4xxW> = 1.04.
Fuse protection
A circuit breaker according to EN 60898-1, 8A, C-characteristic
of the type SIEMENS: 5SY4108-7 must be installed in the supply branch on site. It must be
ensured that the miniature circuit breaker is only operated within the permissible range. The
circuit breaker must be mounted close to the SIDOOR controller at a similar ambient
temperature.
Default topology
Only the SIDOOR controller may be connected to the SITOP PSU8200; additional
consumers are not allowed. The spatial expanse of the used power supply circuit must be
less than 30m.
6.3.2
Installation
A miniature circuit breaker (type SIEMENS: 5SY4108-7) is an absolute requirement for
SITOP PSU8200.
The circuit breaker must be mounted close to the SIDOOR controller (at a similar ambient
1
temperature).
232
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB