SIDOOR functions
3.1 Basic functions
3.1.6

DOOR OPEN (command given via digital inputs)

Description of function
The OPEN DOOR command opens the door according to the configured travel curve as long
as the command is present. The door reaches the OPEN position at slow start speed. Then,
if the OPEN DOOR command is present, the door is held open by the torque that can be
adjusted by the parameter "Continuous torque open".
The OPEN DOOR command has priority over all other control commands.
Note
If the commands CLOSE DOOR and OPEN DOOR are present simultaneously, the door
always moves in the OPEN direction.
SIDOOR ATD410W/ATD420W/ATD430W
See also section Free function blocks (FBLOCK) (Page 76).
Note
As an alternative, the signal can also be evaluated via the PLC (process image).
Connection
SIDOOR ATD401W:
The "OPEN DOOR" function is connected to "Input 3" (X6). See also section Digital input
signals (Page 108).
For the door commands to be given via the digital inputs, "Main menu → General setup →
Special parameters → FBLOCK configuration → Standard input" must be selected in the
operating menu.
Signals
Signal
1 (voltage applied)
0 (voltage not applied)
44
Meaning
The OPEN DOOR command is pending
The OPEN DOOR command is not pending
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB