F512
Accel/Decel Pattern #3
Program
Special Control Parameters
Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the #3 Accel/Decel
parameter.
Settings:
Linear
S-Pattern 1
S-Pattern 2
Accel/Decel Switching Frequency #2
Program
Special Control Parameters
This parameter sets the frequency at which the acceleration control is switched
from the Accel #2 profile to the Accel #3 profile during a multiple-acceleration
profile configuration.
Accel #4 Time
Program
Special Control Parameters
Settings
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to
the Maximum Frequency for the #4 Acceleration profile. The accel/decel
pattern may be set using F502. The minimum accel/decel time may be set using
F508.
Note: An acceleration time shorter than the load will allow may cause nuisance
tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the acceleration
time.
Decel #4 Time
Program
Special Control Parameters
Settings
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency to 0.0 Hz for the #4 Deceleration profile. The accel/
decel pattern may be set using F502. The minimum accel/decel time may be set
using F508.
Note: A deceleration time shorter than the load will allow may cause nuisance
tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the deceleration
time.
H7 ASD Operation Manual
Accel/Decel #1 – #4
Accel/Decel Special
Accel/Decel #1 – #4
Accel/Decel #1 – #4
Direct Access Number — F512
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Direct Access Number — F513
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F514
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Direct Access Number — F515
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
F515
141