F154
OUT5 On Delay
Program
Terminal Selection Parameters
OUT5
This parameter delays the closing of the OUT5 output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
OUT6 On Delay
Program
Terminal Selection Parameters
OUT6
This parameter delays the closing of the OUT6 output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
OUT7 On Delay
Program
Terminal Selection Parameters
OUT7
This parameter delays the closing of the OUT7 output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
OUT1 Off Delay
Program
Terminal Selection Parameters
OUT1
This parameter delays the opening of the OUT1 (A & C) output terminals by
the programmed value.
The delay may be increased to allow the devices that are connected to OUT1 to
respond.
H7 ASD Operation Manual
Output Terminal Delays
Output Terminal Delays
Output Terminal Delays
Output Terminal Delays
Direct Access Number — F154
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F155
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F156
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F160
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F160
75