Clearing A Trip - Toshiba H7 Operation Manuals

Adjustable speed drive
Hide thumbs Also See for H7:
Table of Contents

Advertisement

the oldest recorded trip will be deleted with each new record stored (first-in first-out). The Trip # field
may be selected and scrolled through to view the recorded trip information for a given trip number. The
monitored at-trip parameters are listed in
Trip records zero and one are comprised of the full list of monitored parameters listed in
records 2 – 18 are comprised of the first 16 parameters of
of the first 7 parameters of
Table 8. Trip History Record Parameters (RTC option required).
1) Trip Number
2) Trip Type
3) Time and Date
4) Frequency at Trip
5) Output Current
6) Output Voltage
7) Direction
8) Frequency Reference
Trip Monitor From ASD
The Trip Monitor From ASD function records the trip name of up to four trips and catalogs each trip as
Most Recent, Second Most Recent, Third Most Recent, and Fourth Most Recent. Once reset (Clear
Trip), the trip records are erased. If no trips have occurred since the last reset, No Fault is displayed for
each trip record.
Note:
An improper ASD setup may cause some trips — reset the ASD to the Factory Default
settings before pursuing a systemic malfunction (Program
Type Reset
Trip Record at Monitor Screen
The at-trip condition of the last incurred trip may be viewed at the Monitor screen. The Monitor screen
at-trip record is erased when the ASD is reset.

Clearing a Trip

Once the cause of the trip has been corrected, performing a
operation.
The record of a trip may also be cleared using either of the following methods:
Cycling power (trip info may be saved via
Pressing the Stop|Reset key twice,
Remotely via the communications channel,
Momentarily connecting terminal RES to CC of the Control Terminal Strip, or
Via Program
178
Table 8 on pg. 178
Table
8.
At-trip Recorded Parameters
9) Bus Voltage
10) Discrete Input Status
11) OUT1/OUT2/FL Status
12) Timer
13) Post Compensation Frequency
14) Feedback (inst.)
15) Feedback (1 sec.)
16) Torque
Restore Factory Defaults)
Utility Parameters
Type Reset
as At-trip Recorded Parameters.
Table 8
and trip records 19 – 100 are comprised
17) Torque Reference
18) Torque Current
19) Excitation Current
20) PID Value
21) Motor Overload
22) ASD Overload
23) DBR Overload
24) Motor Load
Utility Parameters
.
Reset
re-enables the ASD for normal
F602
if required),
Clear Trip (clears Trip Monitor From ASD).
Table
8. Trip
25) ASD Load
26) DBR Load
27) Input Power
28) Output Power
29) Peak Current
30) Peak Voltage
31) PG Speed
32) PG Position