F105
R/F Priority Selection
Program
Terminal Selection Parameters
The R/F Priority Selection determines the operation of the ASD if both the R
and F control terminals are activated.
Settings:
Reverse
Suspend
The waveforms below depict the motor response for all combinations of the F
and R terminal settings if the Reverse option is chosen.
The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.
Input Terminal Priority
Program
Terminal Selection Parameters
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Control Terminal Strip even
though the system is in the Local mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Control Terminal Strip will receive priority over
commands from the EOI.
See
F260
for further information on using the Jog function.
See
F250
F252
for further information on DC Injection Braking.
Settings:
Enabled
Disabled
60
Input Special Functions
Input Special Functions
Direct Access Number — F105
Parameter Type — Selection List
Factory Default — Reverse
Changeable During Run — No
Direct Access Number — F106
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No