F150
OUT1 On Delay
Program
Terminal Selection Parameters
⇒
⇒
OUT1
Once the condition is met to close the OUT1 (A & C) output terminals, this
parameter delays the closing of the terminals by the programmed value.
For example, if the OUT1 function is programmed as Overtorque Alarm,
OUT1 will close 2.0 mS (the default value for OUT1 On Delay) after the
overtorque condition occurs.
The delay may be increased to prevent relay chatter.
OUT2 On Delay
Program
⇒
Terminal Selection Parameters
OUT2
⇒
This parameter delays the closing of the OUT2 (A & C) output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
FL On Delay
Program
⇒
Terminal Selection Parameters
⇒
FL
This parameter delays the closing of the FL output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
OUT4 On Delay
Program
⇒
Terminal Selection Parameters
OUT4
⇒
This parameter delays the closing of the OUT4 output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
74
Output Terminal Delays
⇒
⇒
Output Terminal Delays
⇒
Output Terminal Delays
⇒
Output Terminal Delays
Direct Access Number — F150
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F151
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F152
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F153
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
H7 ASD Operation Manual
F153