Mitsubishi Electric IQSS-R-E Reference Manual page 49

Iq sensor solution, melsec iq-r/iq-f/l/q series, got2000, melipc
Table of Contents

Advertisement

Execution method of data restoration
The target device for data restoration can be set with a program.
■Acquiring a right to use
Set a value within the range from 1000H to 1FFFH to SD1435.
Right to use for data backup
• Special relays (SM) and special registers (SD) are used for data restoration.
• To prevent the same special relay (SM) and special register (SD) from being set at the same time, acquiring
a right to use of them for data backup is required.
• To acquire a right to use, specify a value which is not duplicate with values for other request sources to
SD1435, and check that the value set to SD1435 is stored to SD1436.
• Normal operation cannot be assured if the data backup function is performed without confirming the
acquisition of a right to use.
■Setting the restoration setting
1.
Setting a target module type
Set the target module type for data restoration to the lower 8 bits of SD1437.
Target module type
1H: AnyWireASLINK
2.
Setting an execution unit
Set the unit of execution for data restoration to the upper 8 bits of SD1437.
Execution unit
1H: Module unit
2H: ID unit
3.
Selecting a folder for data restoration
Set the number for backup folder name, from which data is to be restored, to SD1438.
Target folder
00 to 99: Target folder specification
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit in the step of 'Setting the execution unit', set the start I/O number of a
target device for data restoration to SD1439.
Target device (Module)
0 to FFH: Start I/O number
• Setting an ID number
When '2H' (ID unit) is set for the execution unit in the step of 'Setting the execution unit', set the ID number of a target device
for data restoration to SD1440.
Target device (ID number)
0 to 255 (0FFH): Output slave
module ID number
512 (200H) to 767 (2FFH): Input/
*1
combined slave module ID number
*1 Specify the address + 512 (200H) for an input/combined slave module.
Description
Set the target module type.
Description
Set this to specify all devices supporting iQSS which are connected to the AnyWireASLINK interface module with the
specified start I/O number.
Set this to specify only the device supporting iQSS with the specified ID number among the devices supporting iQSS
which are connected to the AnyWireASLINK interface module with the specified start I/O number.
Description
Specify the number among the numbers for backup folder name, 00 to 99.
Description
When '1H' (module unit) is set for the execution unit, set the value obtained by dividing the start I/O number of an
AnyWireASLINK master module, which is connected to a target device supporting iQSS, by 16.
Description
When '2H' (ID unit) is set for the execution unit, set the ID number of a target device supporting iQSS.
3.5 Backing up/Restoring Data of Devices Supporting iQSS
3 AnyWireASLINK
47
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

13jv28