Air Supply; Commissioning; Safety Instructions; Checks Prior To Commissioning - ABB PositionMaster EDP300 Operating Instruction

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D

Air supply

*
Instrument air
Purity
Oil content
Pressure dew point
Supply pressure
Air consumption**
*
Free of oil, water and dust in accordance with DIN / ISO 8573-1. Pollution
and oil content n accordance with Class 3
** Independent of supply pressure
Compressed air output
Range
0 to 10 bar (0 to 145 psi)
Air capacity
Standard:
Optional:
Output function
For single acting or double acting actuators
Air is vented from actuator or actuator is
blocked in case of (electrical) power failure
Shut-off values
End position 0 % = 0 to 45 %
End position 100 % = 55 to 100 %
Maximum particle size: 5 m
Maximum particle density: 5 mg/m
Maximum concentration 1 mg/m
10 K below operating temperature
Standard design:
1.4 to 10 bar (20 to 145 psi)
Marine version:
1.5 to 8 bar (22 to 116 psi)
< 0.03 kg/h / 0.015 scfm
3
40 kg/h (31 Nm
/h / 20 scfm)
3
50 kg/h (40 Nm
/h / 23 scfm)

8 Commissioning

Safety instructions

Note
The electrical power supply and supply air pressure data
indicated on the name plate must be complied with during
commissioning.
3
Before switching on the device, make sure that your installation
3
complies with the environmental conditions listed in the chapter
"Technical Data" or on the data sheet.
If there is a chance that safe operation is no longer possible,
take the device out of operation and secure it against
unintended startup.

Checks prior to commissioning

Air pressure in the compressed air connecting line:
1.4 to 10 bar (20 to 145 psi)
Marine version: 1.6 to 8 bar (23 to 116 psi)
Current input active: 4 to 20 mA

Mechanical mounting checks

During commissioning, the mechanical mounting on the linear
and rotary actuators is checked. For this purpose, the actuator is
first moved into the end positions and Auto Adjust is then
carried out.
With large actuators, it can occur that the time for automatic
adjustment is significantly than in smaller actuators.
37