PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
Menu / parameter
Value range
Service (continued)
Remote Sensor*
Off, On
Sensor Type *
Standard
Non-Contact
External Sensor
No Linearization
Sensor Calib.*
Value 1 ... Value 5
Confirm
Sensor Position
0° Position
AO Alarm Current *
Low, High
*
Parameter is only visible if Service Mode is set to 'On'.
Change from one to two columns
Description
If an external position sensor is connected, this parameter must be set to 'On'.
Use this parameter to select the version of the installed position sensor.
Standard – Standard position sensor
Non-Contact – Contactless position sensor.
Once the position sensor has been replaced, the correction values used for linearizing the sensor
characteristic curve (supplied by the factory together with the position sensor) can be entered here. The
entered values are accepted by using 'Confirm'.
Use this parameter to set the fine adjustment of the 0° position after a sensor replacement.
The current position of the sensor range is accepted as a center position by using 'Confirm'.
Note
For this purpose, the positioner feedback shaft must be exactly in the center position.
Use this parameter to set the alarm current for the analog position feedback. This current is output even
if the positioner is in a no-current state (external supply).
High – I > 21.5 mA
Low – I < 3.6 mA
Note
In order to save the parameter in the non-volatile memory on the 'analog position feedback' module, the
module must be supplied with 24 V during parameterization.