Start Automatic Adjustment - ABB PositionMaster EDP300 Operating Instruction

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
Symbol
Operating mode
Manual set point, fixed control
The valve is adjusted manually within the stroke range
using the
1. Press and hold the relevant operating button for the
desired direction.
2. .Additionally, press
to high-speed mode.
CAUTION
Danger of crushing!
Configured stroke limit positions and stroke times
are not effective in manual mode. When the actuator
moves, there is a risk of crushing.
You must make sure that there are no people
present within the operating range of the
actuator.
Moving the actuator manually
The valve is adjusted manually within the valve range
using the
indicator shows the position in angular degrees for the
purpose of checking the mounting conditions.
1. Press and hold the relevant operating button for the
desired direction.
2. .Additionally, press
to high-speed mode.
CAUTION
Danger of crushing!
If air escapes due to a leakage, the position will not
be readjusted. Configured stroke limit positions and
stroke times are not effective in manual mode. When
the actuator moves, there is a risk of crushing.
You must make sure that there are no people
present within the operating range of the
actuator.
Set point via HART, adaptive control
Set point via HART, fixed control
Activated binary input, adaptive control
Activated binary input, fixed control
or
direction buttons.
if the device is to be switched
or
direction buttons. The position
if the device is to be switched

Start automatic adjustment

The Auto Adjust function of the device can be configured and
started in the 'Operating mode' menu.
Process display
1. Use
to switch to the Operating Mode menu.
Operating mode
Auto Adjust
O Adaptive
O Control
O Manual SP
O Manual Sensor
Back
2. .Use
or
to select the 'Adaptive' operating mode.
3. Confirm the selection with
control button for at least 4 seconds (wait for the time to
count down on the top left of the display).
Auto Adjust
Full Auto Adjust
Rotary
Linear
Exit
4. Use
or
to select 'Actuator type'.
Select 'Rotary' for rotary actuators.
Select 'Linear' for linear actuators.
OK
. Press and hold down the
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents