PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
Menu: Digital Input
Menu / parameter
Value range
Input/Output / Digital Input
DI Function
Off
Hold Last SP
Hold User SP
Hold Last Pos.
Vent. Out1
Vent. Out2
Freeze Outputs
Partial Stroke Test
Service Required
Safety Position
Conf. Locked
Panel Locked
Locked
DI Default SP
0 to 100%
DI Logic
Active High, Active Low
Description
Off – No function
Hold Last SP – Last set point is retained
Hold User SP – Substitute value for set point (defined in 'DI Default Setup.')
Hold Last Pos. – Hold previous position
Vent. Out1 – Vent Output 1
Vent. Out2 – Vent Output 2
Freeze Outputs – Close pneumatic outputs
Partial Stroke Test – Start Partial Stroke Test
Service Required – Issue diagnosis bit via binary feedback
Safety Position – Approach safety position
Conf. Locked – Block local configuration
Panel Locked – Block local operation
Locked – Block all operation and setting options.
The position defined using this parameter is approached when the 'Digital Input' function has been set
to 'Hold User SP' and the digital input has been activated.
Use this parameter to configure the contact logic for activating the digital input.
Note
For the following parameters, the contact logic is always 'Active Low' or 'Off':
Safety Position
Conf. Locked
Panel Locked
Locked
63