PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
Menu: Digital Feedback
Menu / parameter
Value range
Input/Output / Digital Feedback
Switch 1
Switch 1 Funct.
Switch 1 Value
Switch 1 Logic
Switch 1 Active
SW 1 Mask Map
Alarm Maintenan.
Alarm OoSpec.
Alarm Check Fct.
Alarm Failure
Switch 1 Sim.
Switch 2
Switch 1 Funct.
Switch 1 Value
Switch 1 Logic
Switch 1 Active
SW 2 Mask Map
Alarm Maintenan.
Alarm OoSpec.
Alarm Check Fct.
Alarm Failure
Switch 2 Sim.
Menu: Switch 1
Menu / parameter
Value range
Input/Output / Digit. Feedback / Switch 1
Switch 1 Funct.
Position Info
Diagnostic State
Switch 1 Value
0 to 100%
Switch 1 Logic
Active High
Active Low
Switch 1 Active
Fall below, Exceeding
Description
The function of switch 1 is configured in this parameter group.
•
Switch 1 Funct. – Switch 1 function
•
Switch 1 Value – Switch 1 value
•
Switch 1 Logic – Switch 1 logic
•
Switch 1 Active – Switch 1 activation.
The function of switch 1 MASK MAP' is configured in this parameter group.
•
SW 1 Mask Map – Switch 1 diagnosis classification
•
Switch 1 Sim. – Switch 1 simulation
The function of switch 2 is configured in this parameter group.
•
Switch 2 Funct. – Switch 2 function
•
Switch 2 Value – Switch 2 value
•
Switch 2 Logic – Switch 2 logic
•
Switch 2 Active – Switch 2 activation.
•
SW 2 Mask Map – Switch 2 diagnosis classification
•
Switch 2 Sim. – Switch 2 simulation
The function of switch '2 MASK MAP' is configured in this parameter group.
•
SW 2 Mask Map – Switch 2 diagnosis classification
•
Switch 2 Sim. – Switch 2 simulation
Description
Use this parameter to select whether the switch is to be used as a limit signal generator or for signaling
diagnostics messages.
•
Position Info – Evaluate position
•
Diagnostic State – Assess diagnosis status
Use this parameter to configure the position value as a limit signal generator. It is taken into account
when the 'Switch 1 Funct.' parameter is set to 'Position Info'.
Use this parameter to select the contact logic.
•
Active High (active) = Output current I > 2.1 mA
•
Active Low (active) = Output current I < 1.2 mA
Use this parameter to select the edge for activating the switch.
•
Off – Deactivated
•
Fall below – If down-scaled
•
Exceeding – If up-scaled
65