ABB PositionMaster EDP300 Operating Instruction page 76

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

76
PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
... 10 Diagnosis / error messages
... Possible error messages
No.
Priority
Fault message
23
59
Leakage in actuator
24
78
Pressure NV Data defect
25
83
Pressure NV chip defect
26
73
Overpressure from supply
27
74
Overpressure from supply
28
75
Supply pressure limit high
exceeded
29
76
Pressure hammer from
supply
30
40
tv up exceeded
31
45
tv down exceeded
32
41
Y-Offset Up exceeded
33
42
Y-Offset Down exceeded
34
61
Friction limit exceeded
35
62
Stiction limit exceeded
36
77
Universal input out of range Input range area up-scaled
37
63
Partial stroke failed
38
64
Option module defect
39
65
Universal input limit
exceeded
40
47
Analog output simulation
active
41
46
Binary output simulation
active
42
97
Fail safe active - via device
error
43
66
Fail safe active - via user
Possible cause
Leakage inside the actuator
Supply air pressure too high
Supply air pressure is too low or
filter is clogged
Supply air pressure too high
Pressure shock in compressed air
supply Supply air pressure too
high
Excessive dynamic friction
Excessive friction
Excessive dynamic friction
Excessive friction
Excessive dynamic friction
Excessive friction
The partial stroke test has failed Check valve.
Defective option module
Universal input limit value up-
scaled
Analog feedback monitor
simulation active
Alarm current binary output
simulation active
Positioner in safety position due
to device failure
Positioner in safety position due
to user action
Troubleshooting the Instrument
Check the actuator diaphragms
Restart device
Replace pressure option
Check supply air pressure
Check supply air pressure or filter
Check supply air pressure
Check air supply
Valve requires maintenance
Valve requires maintenance
Valve requires maintenance
Valve requires maintenance
Valve requires maintenance
Valve requires maintenance
Check parameterization
Replace option module
Depends on application
Terminate simulation.
Terminate simulation.
Check next error message,
determine and eliminate cause.
Switch off service mode
F
C
S
M
X
X
Electronics
X
Electronics
X
Requirements
X
Requirements
X
Requirements
X
X
X
X
X
X
X
X
X
X
Electronics
X
X
X
X
X
Requirements
Group
Actuator
Special
Special
Special
Actuator
Actuator
Actuator
Actuator
Actuator
Actuator
Actuator
Special