PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
Setpoint
Menu / parameter
Value range
Device Setup / Setpoint
SP Range Min.
4.0 to 18.4 mA
SP Range Max.
5.6 to 20.0 mA
SP Filter
0 to 120 seconds
SP Ramp Up
Off up to 0 to 200 seconds
SP Ramp Down
Off up to 0 to 200 seconds
Description
The setpoint range is the range of the input current as a percentage of the operating range of the
fittings from 0 to 100 %.
Use parameter '0' to specify the lower limit for the setpoint range.
Note
The configured setpoint range must not be smaller than 20 % (3.2 mA).
The setpoint range is the range of the input current as a percentage of the operating range of the
fittings from 0 to 100 %.
Use parameter '100' to specify the upper limit for the setpoint range.
Note
The configured setpoint range must not be smaller than 20 % (3.2 mA).
Use this parameter to set a damping value for the setpoint signal.
Here the stroke time for the actuator can be increased.
A setpoint change is not directly transferred to the positioner; instead, the speed is reduced
accordingly.
CAUTION
Danger of crushing!
In manual mode, with an active safety position and after errors, the 'Set point ramp' function is
disabled.
The actuator will therefore move without delay.
Do not reach into the adjustment mechanism.
Here the stroke time for the actuator can be increased.
A setpoint change is not directly transferred to the positioner; instead, the speed is reduced
accordingly.
CAUTION
Danger of crushing!
In manual mode, with an active safety position and after errors, the 'Set point ramp' function is
disabled.
The actuator will therefore move without delay.
Do not reach into the adjustment mechanism.
53