Huawei FusionModule2000 V500R002C03 Maintenance Manual page 30

Smart modular data center
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Cente
Maintenance Guide
Item
Operation
to enter the operating
information page, and
check the
communications, PoE
port connection, and
power supply.
Check the
On the ECC800
availability of the
WebUI, choose
rack environment
Monitoring >
unit.
Cabinet > IT
Cabinet > Rack
Environment Unit to
enter the operating
information page, and
check information such
as communication
status and temperature.
1. On the ECC800
Check the
availability of the
AC actuator.
2. On the ECC800
NOTE
After checking the AC
actuator, set Set light
mode to the status before
you perform 1.
Check the
On the ECC800
availability of the
WebUI, choose
skylight actuator.
Monitoring > Aisle >
Skylight Actuator
Check the
Group > Skylight
availability of the
Actuator to enter the
magnetic lock.
Controls page, and
remotely control the
skylight.
Issue 03 (2019-12-04)
WebUI, choose
Monitoring >
Aisle > AC
Actuator Group >
AC Actuator >
Running
Parameters, set Set
light mode to
Manual, and click
Submit.
WebUI, choose
Monitoring >
Aisle > AC
Actuator Group >
AC Actuator to
enter the Controls
page, and remotely
control the lights.
Copyright © Huawei Technologies Co., Ltd.
Standard
The communication,
temperature, and door
status information of the
rack environment unit are
normally displayed on the
ECC800 WebUI.
Lights in the smart
module aisle can be
normally controlled
through the AC actuator.
The skylight in the smart
module aisle can be
normally controlled
through the skylight
actuator.
4 Routine Maintenance
Troubleshooting
the smart ETH gateway.
If the display is not normal, check
whether the communications cable
is loose or disconnected. If so,
reconnect the cable. If not, replace
the rack environment unit.
If the lights cannot be normally
controlled, check whether the AC
power cable to the lights is loose or
disconnected. If so, reconnect the
cable. If not, replace the AC
actuator.
If the skylight cannot be normally
controlled, check whether the cable
between the skylight magnetic lock
and actuator is in good condition
and securely connected. If not,
replace the skylight magnetic lock
or actuator.