General information about SINAMICS Safety Integrated
1.3 Parameter, Checksum, Version, Password
● Change password for the drives
● Change password for the TM54F
If you need to change safety parameters but you do not know the safety password, proceed
as follows:
1. Set the entire drive unit (Control Unit with all connected drives/components) to the factory
setting.
2. Recommission the drive unit and drives.
3. Recommission Safety Integrated.
Parameter overview for password (see SINAMICS S List Manual)
● p9761 SI password input
● p9762 SI password new
● p9763 SI password acknowledgement
● p10061 SI password input TM54F
● p10062 SI password new TM54F
● p10063 SI password acknowledgement TM54F
20
– p0010 = 95 Commissioning mode
– p9761 = Enter "old safety password".
– p9762 = Enter "new password".
– p9763 = Confirm "new password".
– The new and confirmed safety password is valid immediately.
– p0010 = 95 Commissioning mode
– p10061 = Enter "Old TM54F Safety Password" (factory setting "0")
– p10062 = Enter "new password"
– p10063 = Acknowledge "new password"
– The new and acknowledged safety password is valid immediately.
Function Manual, (FHS) , 07/2007 Edition, 6SL3097-2AR00-0BP0