Siemens SINAMICS S120 Function Manual page 84

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
6.3 PROFIsafe network transition with SIMOTION D
Figure 6-14
3. Enable the SOS and SLS functions, click the "Configuration" button and then enter the
PROFIsafe address of the drive in hexadecimal notation at the already defined parameter
F_Dest_Add in the configuration screen (refer to the chapter "Configuring PROFIsafe
communication", item 10).
Figure 6-15
4. Click "Copy parameters" and then click "Activate settings". Click "Entire project" to save
your settings.
84
Activating PROFIsafe settings
PROFIsafe configuration, PROFIsafe address for the drive
Function Manual, (FHS) , 07/2007 Edition, 6SL3097-2AR00-0BP0